RICS-M

The product is designed to equip the supplying feeder cells of the high voltage line and it is mounted in the automation units from the traction sub-stations.
Rated supply voltage: 48Vdc(-30%, +25%) Power consumption on the current circuit: 8,5VA Power consumption on the voltage circuit: 9,5VA Long time maximum admissible current: 1,5In(30 minutes) Long time admissible voltage: 1,2Un Maximum admissible current: 20In Maximum sensitivity angle: 60°-80° Protection degree: IP30 Dimensions: 220x180x165 mm Operating temperature: -25°C...+70°C Anticorrosive padding.